Protection of Transformers
Transformers are static devices, totally enclosed and generally oil immersed. Therefore, chances of faults occurring on them are very rare. However, the consequences of even a rare fault may be very serious unless the transformer is quickly disconnected from the system. This necessitates to provide adequate automatic protection for transformers against possible faults.
Small distribution transformers are usually connected to the supply system through series fuses instead of circuit breakers. Consequently, no automatic protective relay equipment is required. However, the probability of faults on power transformers is undoubtedly more and hence automatic protection is absolutely necessary.
Common Transformer Faults : As compared with generators, in which many abnormal conditions may arise, power transformers may suffer only from :
(i) open circuits
(ii) overheating
(iii) winding short-circuits e.g. earth-faults, phase-to-phase faults and inter-turn faults.
An open circuit in one phase of a 3-phase transformer may cause undesirable heating. In practice, relay protection is not provided against open circuits because this condition is relatively harmless. On the occurrence of such a fault, the transformer can be disconnected manually from the system.
Overheating of the transformer is usually caused by sustained overloads or short-circuits and very occasionally by the failure of the cooling system. The relay protection is also not provided against this contingency and thermal accessories are generally used to sound an alarm or control the banks of fans.
Winding short-circuits (also called internal faults) on the transformer arise from deterioration of winding insulation due to overheating or mechanical injury. When an internal fault occurs, the transformer must be disconnected quickly from the system because a prolonged arc in the transformer may cause oil fire. Therefore, relay protection is absolutely necessary for internal faults.
Protection Systems for Transformers
For protection of generators, Merz-Price circulating-current system is unquestionably the most satis factory. Though this is largely true of transformer protection, there are cases where circulating current system offers no particular advantage over other systems or impracticable on account of the troublesome conditions imposed by the wide variety of voltages, currents and earthing conditions invariably associated with power transformers. Under such circumstances, alternative protective systems are used which in many cases are as effective as the circulating-current system. The principal relays and systems used for transformer protection are:
(i) Buchholz devices provide protection against all kinds of incipient faults i.e. slow-developing faults such as insulation failure of windings, core heating, fall of oil level due to leaky joints etc.
(ii) Earth-fault relays providing protection against earth-faults only.
(iii) Overcurrent relays providing protection mainly against phase-to-phase faults and overloading.
(iv) Differential system (or circulating-current system) providing protection against both earth and phase faults.
The complete protection of the transformer usually requires the combination of these systems. Choice of a particular combination of systems may depend upon several factors such as (a) size of the trans former (b) type of cooling (c) location of transformer in the network (d) nature of load supplied and (e) importance of service for which transformer is required.
Buchholz Relay
Buchholz relay is a gas-actuated relay installed in oil immersed transformers for protection against all kinds of faults. Named after its inventor, Buchholz, it is used to give an alarm in case of incipient (i.e. the transformer and to disconnect the transformer from the supply in the event of severe internal faults. It is usually installed in the pipe connecting the conservator to the main tank. It is a universal practice to use Buchholz relays on all such oil immersed transformers having ratings in excess of 750 kVA.
Construction : It takes the form of a domed vessel placed in the connecting pipe between the main tank and the conservator. The device has two elements. The upper element consists of a mercury type switch attached to a float. The lower element contains a mercury switch mounted on a hinged type flap located in the direct path of the flow of oil from the transformer to the conservator. The upper element closes an alarm circuit during incipient faults whereas the lower element is arranged to trip the circuit breaker in case of severe internal faults.
Operation : The operation of Buchholz relay is as follows:
(i) In case of incipient faults within the transformer, the heat due to fault causes the decomposition of some transformer oil in the main tank. The products of decomposition contain more than 70% of hydrogen gas. The hydrogen gas being light tries to go into the conservator and in the process gets entrapped in the upper part of the relay chamber. When a predetermined amount of gas gets accumulated, it exerts sufficient pressure on the float to cause it to tilt and close the contacts of the mercury switch attached to it. This completes the alarm circuit to sound an alarm.
(ii) If a serious fault occurs in the transformer, an enormous amount of gas is generated in the main tank. The oil in the main tank rushes towards the conservator via the Buchholz relay and in doing so tilts the flap to close the contacts of the mercury switch. This completes the trip circuit to open the circuit breaker controlling the transformer.
Advantages
(i) It is the simplest form of transformer protection.
(ii) It detects the incipient faults at a stage much earlier than is possible with other forms of protection.
Disadvantages
(i) It can only be used with oil immersed transformers equipped with conservator tanks.
(ii) The device can detect only faults below oil level in the transformer. Therefore, separate protection is needed for connecting cables.
Circulating-Current Scheme for Transformer Protection
Merz-Price circulating-current scheme R for the protection of a 3 phase delta/delta power Y transformer against phase-to ground and phase-to-phase B faults is shown in figure. Note that CTs on the two sides of the transformer are connected in star. This compensates for the phase difference between the power transformer primary and secondary. The CTs on the two sides are connected by pilot wires and one relay is used for each pair of CTs.
During normal operating conditions, the secondaries of CTs carry identical currents. Therefore, the currents entering and leaving the pilot wires at both ends are the same and no current flows through the relays. If a ground or phase-to-phase fault occurs, the currents in the secondaries of CTs will no longer be the same and the differential current flowing through the relay circuit will clear the breaker on both sides of the transformer. The-protected zone is limited to the region between CTs on the high-voltage side and the CTS on the low-voltage side of the power transformer.
It is worthwhile to note that this scheme also provides protection for short-circuits between turns on the same phase winding. When a short-circuit occurs between the turns, the turn-ratio of the power transformer is altered and causes unbalance between current transformer pairs. If the turn-ratio of the power transformer is altered sufficiently, enough differential current may flow through the relay to cause its operation. However, such short-circuits are better taken care of by Buchholz relays.
0 Comments